Type: | Insulated |
---|---|
Conductor Type: | Stranded |
Application: | Heating |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Solar cables applies to flexible single-core cables (cords) for use at the DC-side of photovoltaic systems with a maximum permissible voltage of DC 1.8 kV (conductor/conductor, non-earthed system).The cables are suitable for use in safety class II. It is permitted to connect these cables as multiple-construction. The cables are intended to operate at ambient temperature until 90°C
H 1Z2Z2-K Cable structure parameters Table 1
specifications mm2 |
Conductor diameter of mm | Nominal thickness of the insulation is mm | Nominal thickness of the sheath is mm | The cable has an approximate outer diameter of mm | The approximate weight of the cable is kg / km | The maximum DC resistance of the 20ºC conductor is Ω / km |
1×1.5 | 1.58 | 0.7 | 0.8 | 4.6 | 35 | 13.7 |
1×2.5 | 2.02 | 0.7 | 0.8 | 5.0 | 47 | 8.21 |
1×4 | 2.58 | 0.7 | 0.8 | 5.6 | 65 | 5.09 |
1×6 | 3.17 | 0.7 | 0.8 | 6.2 | 87 | 3.39 |
1×10 | 4.1 | 0.7 | 0.8 | 7.6 | 132 | 1.95 |
1×16 | 5.6 | 0.7 | 0.9 | 8.8 | 197 | 1.24 |
1×25 | 7.1 | 0.9 | 1.0 | 10.9 | 303 | 0.795 |
1×35 | 8.5 | 0.9 | 1.1 | 12.5 | 410 | 0.565 |
1×50 | 10.2 | 1.0 | 1.2 | 14.6 | 573 | 0.393 |
1×70 | 12.0 | 1.1 | 1.2 | 16.6 | 777 | 0.277 |
1×95 | 14.0 | 1.1 | 1.3 | 18.8 | 1030 | 0.210 |
1×120 | 16.0 | 1.2 | 1.3 | 21.0 | 1284 | 0.164 |
1×150 | 17.0 | 1.4 | 1.4 | 22.6 | 1594 | 0.132 |
1×185 | 19.0 | 1.6 | 1.6 | 25.4 | 1979 | 0.108 |
1×240 | 22.0 | 1.7 | 1.7 | 28.8 | 2540 | 0.0817 |
way to install | Single cable is in the air | Single cable on the object surface | Two contacting cables are on the surface of the object |
section mm2 | current-carrying capacity A | ||
1.5 | 30 | 29 | 24 |
2.5 | 41 | 39 | 33 |
4 | 55 | 52 | 44 |
6 | 70 | 67 | 57 |
10 | 98 | 93 | 79 |
16 | 132 | 125 | 107 |
25 | 176 | 167 | 142 |
35 | 218 | 207 | 176 |
50 | 276 | 262 | 221 |
70 | 347 | 330 | 278 |
95 | 416 | 395 | 333 |
120 | 488 | 464 | 390 |
150 | 566 | 538 | 453 |
185 | 644 | 612 | 515 |
240 | 775 | 736 | 620 |
working temperature | 120ºC | ||
ambient temperature | 60ºC |
Ambient temperature (ºC) (in the air) | 60ºC and below | 70 | 80 | 90 | 100 | 110 |
coefficient of correction | 1.00 | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
MODEL | PV1-F |
Conductor | Tinned copper wire,class 5 (as per IEC 60228) |
Insulation | No Halogen PO insulation |
Sheath | No Halogen PO sheath |
rated voltage | AC 0.6/1KV |
DC 1.8KV | |
Temperature range | -40°C~+90°C,dry/ humidity |
Max.working temperature of conductor | 120°C |
During short circuit | 200°C |
Standard | EN 2PFG 1169 |