0.6 / 1kV copper core XLPE insulated Marine Fire resistance cable flexible wire
Detailed Photos

Product Parameters
Cable model
CBYJR/N C-0.6/1kV
Rated voltage (U0 / U)
0.6/1kV
maximum system voltage (Um)
1.2kV
scope of application
This product is suitable for all kinds of river and sea ships and offshore oil platforms and other water buildings transmission power.
construction of cable
electric conductor
The fifth tin-plated soft copper conductor
Fire resistance layer (for CBYJR / NC only)
Two layers of gold mica tape
insulation
Irradiated low-smoke halogen-free flame retardant polyolefin insulation
product standard
NEK TS 606:2009
Specifications range
1 core: 0.5~120 mm2
Insulation color
Black / gray / red / blue
Other colors can be negotiated according to the buyers demand
technical parameter
temperature grade
In normal use, the maximum operating temperature of the conductor is 90ºC
Ambient temperature: -40ºC ~ + 50ºC
Cable laying temperature: not less than 0ºC (if the ambient temperature is less than 0ºC, the cable shall be preheated)
minimum bending radius
Single core cable: D 25 mm, minimum bending radius of 4D
D> 25 mm with a minimum bending radius of 6 D
(D is the actual outer diameter of the cable)
Laying method
Pipe-through laying, shallow trough laying, tunnel laying, interlayer laying, deck laying, etc.
Product surface identification
Model and voltage specification of Shanghai Qifan Cable Co., Ltd
CBYJR / N C-0.6/1kV Cable structure parameters Table 1
specifications mm2 |
The conductor monofilament diameter is mm |
Conductor diameter of mm |
Insulation nominal thickness mm |
The cable has an approximate outer diameter of mm |
The approximate weight of the cable is kg / km |
1×0 .5 |
0 .20 |
0.92 |
0.7 |
3.2 |
11.4 |
1×0.75 |
0 .20 |
1.13 |
0.7 |
3.4 |
14.4 |
1×1.0 |
0 .20 |
1.30 |
0.7 |
3.6 |
17.3 |
1×1.5 |
0 .20 |
1.57 |
0.7 |
3.9 |
22.8 |
1×2.5 |
0 .20 |
2.02 |
0.7 |
4.3 |
33.3 |
1×4 |
0 . 3 0 |
2.59 |
0.7 |
4.9 |
48.8 |
1×6 |
0 . 3 0 |
3.17 |
0.7 |
5.5 |
68.8 |
1×10 |
0 . 4 0 |
4.1 |
0.7 |
6.5 |
107.8 |
1×16 |
0 .40 |
5.5 |
0.7 |
8.0 |
166.4 |
1×25 |
0 .40 |
6.7 |
0.9 |
9.7 |
256.7 |
1×35 |
0 .40 |
8.2 |
0.9 |
11.2 |
352.1 |
1×50 |
0 .40 |
10 |
1.0 |
13.3 |
497.4 |
1×70 |
0 .40 |
11.6 |
1.1 |
15.2 |
687.2 |
1×95 |
0 .40 |
13.5 |
1.1 |
17.2 |
919.0 |
1×120 |
0 .40 |
14.4 |
1.2 |
18.4 |
1151.3 |
Table 2 of CBYJR / D C-0.6/1kV and CBYJR / N C-0.6/1kV cables in air
Core number section |
Single core |
current-carrying capacity A |
1.5 |
23 |
2.5 |
4 0 |
4 |
5 1 |
6 |
5 2 |
10 |
7 2 |
16 |
9 6 |
25 |
1 27 |
35 |
1 57 |
50 |
1 96 |
70 |
2 42 |
95 |
2 93 |
120 |
3 39 |
working temperature |
90ºC |
ambient temperature |
45ºC |
Note: 1) The cables should contact each other when the triangle arrangement;
2) The outer diameter of the cable with the cable center spacing that is 2 times during the plane arrangement;
3) Separation and laying of a single cable (i. e., the adjacent cable has no thermal effect on the cable).
Correction coefficient of load rate with different ambient temperature Table 3
The conductor operating temperature is (ºC) |
Ambient temperature (ºC) (in the air) |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
90 |
1.10 |
1.05 |
1.00 |
0.94 |
0.88 |
0.82 |
0.74 |
0.67 |
CBYJR / D C-0.6/1kV, CBYJR / N C-0.6/1kV cable conductor DC resistance table 4
section mm2 |
The maximum DC resistance of the conductor is Ω / km at 20ºC |
0.5 |
4 0.1 |
0.75 |
2 6.7 |
1.0 |
2 0.0 |
1.5 |
1 3.7 |
2.5 |
8 .21 |
4 |
5 .09 |
6 |
3 .39 |
10 |
1 .95 |
16 |
1.24 |
25 |
0 .795 |
35 |
0 .565 |
50 |
0 .393 |
70 |
0 .277 |
95 |
0 .210 |
120 |
0 .164 |
Features:
------Our Feature------
- Imported equipment with experienced technical team
The company have three plant and has 3048 employees which have 206 engineers. Plant has a series of imported production lines including Niehoff copper drawing lines, Troster Germany and Maillefer Finland 500KV VCV lines, stranding machine from Pourtier France, SKET Germany, Caballe Spain, 220KV and 35KV production line plus SIKORA X - RAY 8000 on-line eccentricity measuring unit from Germany
- Complete certification system
Qifan Cable have gotten ISO 9001, ISO 14001, OHSAS 18001. Plant passed TUV, VDE, UL, CE, SAA, BS etc. certificate.
- Perfect Production system
Qifan Cable products cover LV power cable, MV power cable, HV&EHV power cable, ABC cables, ACSR/AAC/AAAC/ACAR/OPGW ,submarine cable, control cable, instrumentation cable, building wire, flexible rubber cable, fire rated cable, renewable cable, solar cable, industrial cable, Lan cable, coaxial cable etc.
- Perfect Sales service system
Qifan Cable can offer the OEM/ODM service, Multiple products, Skilled Export sale engineer team, Reasonable price, Reliable quality, Friendly service. Qifan is always your best choice.