Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| Application: | Overhead |
| Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| Code* Word | Phase Conductor | Bare Neutral Messenger | Weight per 1000 ft. (lbs.) |
Allowable Ampacities+ |
||||||
| Size (AWG) |
Strand- ing |
Insul. Thick. (mils) |
Size (AWG) |
Strand-ing | Rated Strength (lbs.) |
XLP | POLY | XLP | POLY | |
| ACSR NEUTRAL-MESSENGER | ||||||||||
| Setter | 6 | 1 | 45 | 6 | 6/1 | 1190 | 72 | 72 | 85 | 70 |
| Shepherd | 6 | 7 | 45 | 6 | 6/1 | 1190 | 75 | 75 | 85 | 70 |
| Eskimo | 4 | 1 | 45 | 4 | 6/1 | 1860 | 110 | 110 | 115 | 90 |
| Terrier | 4 | 7 | 45 | 4 | 6/1 | 1860 | 115 | 115 | 115 | 90 |
| Chow | 2 | 7 | 45 | 2 | 6/1 | 2850 | 176 | 176 | 150 | 120 |
| Bull | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 280 | 280 | 205 | 160 |
| * Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP). | ||||||||||
| + Conductor temperature of 90ºC for XLP, 75ºC for Poly; ambient temperature of 40ºC;emissivity 0.9; 2 ft./sec. wind in sun. | ||||||||||
| Triplex Service Drop | |||||||||||
| Code* Word | Phase Conductor | Bare Neutral Messenger | Weight per 1000 ft. (lbs.) |
Allowable Ampacities+ |
|||||||
| Size (AWG) |
Strand- ing |
Insul. Thick. (mils) |
Equiv. Dia. (AWG)++ |
Size++ (kcmil) |
Strand-ing | Rated Strength (lbs.) |
XLP | POLY | XLP | POLY | |
| 6201 ALLOY NEUTRAL-MESSENGER | |||||||||||
| Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
| Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
| Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
| Bamacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
| Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
| Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
| Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
| Dungenese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 483 | 483 | 235 | 185 |
| Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
| Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
| Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
| Code* Word | Phase Conductor | Bare Neutral Messenger | Weight per 1000 ft. (lbs.) |
Allowable Ampacities+ |
||||||
| Size (AWG or kcmil) |
Strand- ing |
Insul. Thick. (mils) |
Size (AWG or kcmil) |
Strand-ing | Rated Strength (lbs.) |
XLP | POLY | XLP | POLY | |
| AAC NEUTRAL-MESSENGER | ||||||||||
| Clydesdale | 4 | 1 | 45 | 4 | 7 | 881 | 198 | 198 | 100 | 80 |
| Pinto | 4 | 7 | 45 | 4 | 7 | 881 | 211 | 211 | 100 | 80 |
| Mustang | 2 | 7 | 45 | 2 | 7 | 1350 | 318 | 318 | 135 | 105 |
| Criollo | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 503 | 503 | 180 | 140 |
| Percheron | 1/0 | 9 | 60 | 2/0 | 7 | 2510 | 619 | 619 | 205 | 160 |
| Hanovarian | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 764 | 764 | 235 | 185 |
| Oldenburg | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 945 | 945 | 275 | 210 |
| Lippizaner | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1519 | 1519 | 370 | 280 |