Application: | Construction, Overhead, Underground, Industrial, Power Station |
---|---|
Voltage: | Medium Voltage Cable |
Current: | DC & AC |
Still deciding? Get samples of US$ 0/Meter
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MultiCore: Steel Wire Armoured (SWA)
Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655
Colour: Red or Black
2. Using features
1. Rated voltage: Uo/U:3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
2. No. of core: Single-core or three cores.
3. The highest allowed operating temperature of conductor for long-term working is 90oC. In short-circuit (Max. long-term is no more than 5 seconds). The highest temperature for a conductor is no more than 250ºC.
4. D.C. resistance of the conductor complies with the stipulations of 3.6/6kV, 6/10kV(11kV), 12/20kV(24kV), 19/33kV, 26/35kV(35kV).
5. The environment temperature should be no lower than 0oC when lay. Otherwise, it should be preheated.
6. The cable is laid without a horizontal drop limit.
7. Working Frequency Voltage Test: 3.5Uo/5min without puncture.
8. Partial Discharge Test: The discharge volume should be no more than 10pC under 1.73Uo for the cable.
9. Minimum Bending Radius: Single core - Fixed: 15 x overall diameter;3 core - Fixed: 12 x overall diameter
(Single core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)
Note: The single-core armored cables are used for the D.C. system only. If used for the A.C. system, the magnetic isolation should be applied to the steel armor wires of non-magnetical materials that should be used.
Item | Category A ,B | 3.6/6kV | 6/10kV | 8.7/15kV | 12/20kV | 18/30kV | 21/35kV |
Category A ,B | 6/6kV | 8.7/10kV | 12/15kV | 18/20kV | - | 26/35kV | |
Single core | mm2 | 25-1200 | 25-1200 | 35-1200 | 50-1200 | 50-1200 | 50-1200 |
Three core | mm2 | 25-400 | 25-400 | 35-400 | 50-400 | 50-400 | 50-400 |
Type | Designation | Applications | |
YJV | Copper conductor,XLPE insulated,PVC sheathed power cable | For laying indoors,in tunnel or cable trench,unable to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. | |
YJLV | Aluminum conductor,XLPE insulated,PVC sheathed power cable | ||
YJY | Copper conductor, XLPE insulated,PE sheathed power cable | ||
YJLY | Aluminum conductor, XLPE insulated,PE sheathed power cable | ||
YJV22 | Copper conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable | For laying indoors,in tunnel in cable trench,or direct in ground,able to bear external mechanical forces.Single core cable is not allowed to laid in magnetic duct. | |
YJLV22 | Aluminum conductor,XLPE insulated,steel tape armoured,PVC sheathed power cable | ||
YJV23 | Copper conductor,XLPE insulated,steel tape armoured,PE sheathed power cable | ||
YJLV23 | Aluminum conductor,XLPE insulated,steel tape armoured,PE sheathed power cable | ||
YJV32 | Copper conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable | For laying indoors,in tunnel cable trench,well or direct in ground,able to bear external mechanical forces and certain pulling force. | |
YJLV32 | Aluminum conductor,XLPE insulated,steel wire armoured,PVC sheathed power cable | ||
YJV33 | Copper conductor,XLPE insulated,steel wire armoured,PE sheathed power cable | ||
YJLV33 | Aluminum conductor,XLPE insulated,steel wire armoured,PE sheathed power cable |